Infrared early-warning model for self-ignition of aluminum powder, magnesium powder, and aluminum-magnesium mixed powders

Su Xingyu, Li Weijia, Jiang Guanyu, Zhong Shengjun

School of Metallurgy, Northeastern University, Shenyang 110819, China

Abstract

Objective Early warning of self-ignition in accumulated metal dust requires distinguishing continuously developing precursors from transient thermal disturbances and high-temperature non-ignition processes. Fixed temperature thresholds mainly reflect absolute temperature levels and may therefore cause false alarms or delayed warnings. To improve warning reliability, a three-stage infrared early-warning method is developed for aluminum, magnesium, and aluminum–magnesium mixed dusts by combining precursor prediction probability, temporal persistence, and temperature-field structural evolution. The method is intended to reduce false alarms caused by high-temperature disturbances while retaining sufficient warning lead time for early intervention.

Methods A controlled heating and infrared monitoring platform was established to obtain 45 independent temperature-field sequences from aluminum dust, magnesium dust, and aluminum-magnesium mixed dust with an 8:2 mass ratio. Five median particle sizes (100, 75, 45, 38, and 30 μm) were tested, with three repetitions performed at each particle-size level. Temperature statistics, spatial-gradient characteristics, Shannon entropy, high-temperature connected-region characteristics, and temporal derivative features were extracted from two-dimensional infrared temperature matrices. For ignition experiments, the precursor period was defined retrospectively from the time at which a sustained open flame first appeared. An extreme gradient boosting (XGBoost) model was used to map multidimensional infrared features to precursor-period labels and output frame-level precursor prediction probabilities. A 30-frame retrospective window was then used to calculate the high-confidence hit ratio, which was defined as the proportion of frames with precursor prediction probabilities of at least 0.95. When the hit ratio reached the temporal-persistence threshold, a candidate alarm was generated. Finally, the second-order difference in the 95% quantile of temperature-gradient magnitude was used as a structural-evolution indicator to screen high-temperature stagnation disturbances. Leave-one-experiment-out cross-validation was adopted, and event recall rate, non-ignition false-alarm rate, and mean warning lead time were evaluated.

Results and Discussion With a 60 s precursor window, discrimination based on precursor prediction probability achieved an event recall rate of 93.33%, a non-ignition false-alarm rate of 33.33%, and a mean warning lead time of 42.1 s. After the temporal-persistence constraint was introduced, the event recall rate remained at 93.33%, while the false-alarm rate decreased to 26.67% and the mean warning lead time was 41.3 s. After structural-evolution screening, the event recall rate was 90.00%, the false-alarm rate decreased to 6.67%, and the mean warning lead time remained at 40.8 s. For precursor-window lengths of 30, 60, and 120 s, the event recall rate was 90.00% in all cases, whereas the false-alarm rates were 13.33%, 6.67%, and 40.00%, respectively. The 60 s window therefore provided a better balance between false-alarm control and warning lead time. Typical thermal-evolution cases showed that ignition samples exhibited sustained high precursor probabilities and continuous structural enhancement, transient-disturbance samples showed only short-lived increases in probability, and high-temperature stagnation samples maintained high probabilities without sustained structural evolution.

Conclusion The proposed three-stage method progressively uses single-frame precursor information, temporal persistence, and spatial structural evolution to distinguish developing self-ignition precursors from transient disturbances and high-temperature non-ignition processes. The final event recall rate is 90.00%, the non-ignition false-alarm rate is 6.67%, and the mean warning lead time is 40.8 s. The results indicate that sustained thermal responses and continuous temperature-field structural evolution provide useful complementary information for reliable, non-contact infrared early warning of self-ignition in accumulated reactive metal dust.

Keywords: metal dust; self-ignition early-warning; infrared thermal imaging; temperature field; cascade discrimination

Get Citation:Su Xingyu, Li Weijia, Jiang Guanyu, et al. Infrared early-warning model for self-ignition of aluminum powder, magnesium powder, and aluminum-magnesium mixed powders[J]. China Powder Science and Technology, 2027, 33(4): 1-11.

Received:2026-06-30, Revised: 2026-10-12, Online: 2026-11-25。

Funding: The research was supported by the National Key R&D Program of China (Grant No. 2023YFC3010603).

DOI:10.13732/j.issn.1008-5548.2027.04.001

CLC No.:X932; TB44

Type Code:A

Serial No.:1008-5548(2027)04-0001-11